KYN28A-12 Switchgear is an indoor metal-clad withdrawable assembly for three-phase AC power distribution. Compare the selected voltage variant, busbar and feeder ratings, fault duty and service conditions before defining the lineup.
KYN28A-12 Switchgear Specifications
Electrical Ratings
| Parameter | Unit | Series data |
|---|---|---|
| Rated voltage | kV | 12; a 24 kV variant is listed separately in the series documentation |
| Rated frequency | Hz | 50; 50/60 Hz availability depends on the selected variant |
| Main busbar rated current | A | 630, 1250, 2000, 2500, 3150, 4000; up to 5000 for specified variants |
| Branch busbar rated current | A | 630, 1250, 2000, 2500, 3150, 4000 |
| Rated short-time withstand current (4 s) | kA | 16, 20, 25, 31.5, 40, 50 |
| Rated peak withstand current | kA | 50, 63, 80, 100, 125 |
| Rated short-circuit duration | s | 4 |
Service Conditions
| Parameter | Condition |
|---|---|
| Maximum ambient temperature | +40 °C |
| Minimum ambient temperature | −10 °C; −15 °C or −25 °C for specified variants |
| Daily average temperature | ≤ +35 °C |
| Daily average relative humidity | ≤ 95% |
| Monthly average relative humidity | ≤ 90% |
| Altitude | 1000 m; 2000–3000 m for specified variants |
Ratings are series options, not a single combined configuration. Confirm the voltage variant, current rating, fault level and service conditions when requesting a quotation.
Selection questions for KYN28A-12
Does a 10 kV network require a different model name?
Network nominal voltage and equipment rated voltage are different quantities. Compare the specified network conditions with the selected 12 kV equipment variant and insulation levels. The 10 kV versus 12 kV guide explains what to check; it does not establish suitability from the model suffix alone.
Which values define the offered lineup?
Identify the busbar and feeder currents, fault duty and duration, breaker/protection arrangement, cable interfaces and service conditions on one technical schedule. Do not combine the highest options in the series table into an assumed configuration.
Review substation applications and define the drawings, inspections and records with the factory acceptance checklist. Prepare the enquiry inputs before requesting a configuration.