Home / Products

SIVACON 8PT Low-Voltage Switchgear

SIVACON 8PT is a modular low-voltage switchgear family for incoming distribution, outgoing feeders and motor-control applications. Main horizontal busbars and vertical feeder busbars have different ratings and are specified separately. Cabinet height, compartment design, circuit requirements and installation conditions determine the selected configuration. The series data below distinguishes these parts instead of treating every maximum as one universal cabinet rating.

Send the model, required ratings, quantity, installation conditions and destination. Include a single-line diagram or specification when available.

SIVACON 8PT Switchgear is a low-voltage family for incoming distribution, outgoing feeders and motor-control applications. Separate main and distribution busbar values, circuit duties and service conditions when agreeing the assembly configuration.

SIVACON 8PT Switchgear Specifications

Main Horizontal Busbar Options

Configuration Rated current
2200 mm cabinet height Up to 4000 A
2600 mm cabinet height Up to 7400 A

Main Horizontal Busbar Short-Circuit Options

Parameter Specification / configuration
Rated short-time withstand current Up to 150 kA for 1 s, for the applicable configuration
Rated peak withstand current Up to 375 kA, for the applicable configuration

Vertical Feeder Busbars

Parameter Specification / configuration
Withdrawable-cabinet current 1200 A in the supplied configuration data
Fixed-cabinet current 1500 A in the supplied configuration data
Short-time withstand current options 50 / 65 kA for 1 s, depending on feeder construction
Peak withstand current options 110 / 163 kA, depending on feeder construction

Ratings and options apply to the selected configuration. The agreed drawings and equipment schedule define the supplied assembly.

Separate the busbar duties

The main horizontal busbar distributes power along the lineup. Vertical busbars and feeder connections supply particular circuit arrangements, so their rated current and short-circuit duty need not equal those of the main busbar. The quotation and drawings identify the relevant construction for each section.

Specify access and circuit functions

Define incoming and coupling breakers, outgoing feeder sizes, motor-control functions, metering and cable entry. Available footprint, front or rear access, enclosure protection and the required internal separation should be considered alongside the electrical ratings. Documentation is selected for the agreed equipment arrangement and supply scope.

Information for Selection

  • Required horizontal busbar rating and cabinet height
  • Feeder technology and vertical busbar requirements
  • Fault level and duration for each relevant circuit
  • Access, cable entry, separation and documentation requirements

Explore the application solutions for your industry and include the project specification with your enquiry.